YJV26/35KV 3*240高壓交聯電纜載流量及價格
6kV~35kV 中低壓銅芯及鋁芯交聯聚乙烯絕緣電力電纜(YJV電纜,YJV22電纜,YJLV電纜,YJLV22電纜) XLPE Insulated Power Cable |
YJV26/35KV 3*240高壓交聯電纜載流量及價格交聯聚乙烯絕緣電力電纜是采用化學方法或物理方法,使聚乙烯分子由線型分子結構轉變為三維網狀結構,由熱塑性的聚乙烯變成熱固性的交聯聚乙烯,從而提高了聚乙烯的耐老化性能、機械性能和耐環境能力,并保持了優良的電氣性能。 /5960111 交聯聚乙烯絕緣電力電纜導體的允許長期zui高溫為90攝氏度,較低絕緣電纜、聚氯乙烯絕緣電纜和聚乙烯絕緣電纜高,且具有重量輕、結構簡單、使用方便、耐化學腐蝕和敷設不受落差限制等優點。 26/35KV電力電纜,18/30KV交聯電纜,12/20KVYJV電纜,8.7/15KVYJV22電纜線,6/10KV鋁芯交聯電纜線,3.6/6KVYJLV單芯電纜 中低壓交聯電纜產品標準 Standard /5960111 本產品按GB12706《額定電壓35V及以下銅芯、鋁芯塑料絕緣電力電纜》標準生產,同時還可根據用戶需要按電工委員會推薦標準IEC、英國標準、德國標準及美國標準生產。 The product is manufactured according to the standard of《GB12706 or IEC、BS、DIN and ICEA upon request. 適用范圍 Applications /5960111 本產品適用于工頻額定電壓3.6/6kv~26/35kv輸配電線路作配送電能子用。 The product is suitable for use in power transmission and distribution lines with rated power frequency voltage 3.6/6kv~26/35kv. /5960111 使用特性 Operating characteristics · 工頻額定電壓U0/U為3.6/6kv~26/35kv。 Rated power-frepuency voltage U0/U: 3.6/6kv~26/35kv. · 電纜導體的zui高允許工作溫度:90℃。 Max.admissible operating temperature of the conductor:90℃. · 短路時(zui長時間不超過5s)電纜導體的zui高溫度不超過2500C。 Max. short-circurt temperature of conductor shall not exceed 2500C. (5s maximum duration) /5960111 · 電纜敷設時環境溫度應不低于00C。 The ambient temperature under installation should not below 00C. · 電纜彎曲半徑:三芯電纜不小于電纜外徑15倍;單芯電纜不小于電纜外徑20倍。 The bending radius of a single-core cable should not less than 20 times of the cable diameter. The bending radius of a single-core cable should not less than 15 times of the cable diameter. 電纜額定電壓的選擇 Voltage designation · 電纜的額定電壓應適合于電纜系統的運行狀況,用U0/U(Um)kv表示。 U0-電纜設計用的導體對地或金屬屏蔽之間的額定工頻電壓; U-電纜設計用的導體間的額定工頻電壓; Um-設備可承受的“zui高系統電壓"的zui大值。 The rated voltage of the cable for a given applixation shall be suitable for the operating conditions in the system in which the cable is used,and is expressed in the form of U0/U(Um)kv Where: U0-The rated power-frequency voltage between conductors and earth metallic screen ,for which the cable designed; U - The rated power-frequency voltage between conductos, for which the cable designed; Um- The maximum value of the“highest system voltage"for which the equipment may beused. · 三相系統用電纜的U0值推薦如下表: The values of U0 recommened for cable to be used in three-phase systems are listed below: |
U kv | U m kv | U 0 * kv | A 和 B 類系統 System categories A and B | C 類系統 Systems categories C | 6 | 7.2 | 3.6 | 6 | 10 | 12 | 6 | 8.7 | 15 | 17.5 | 8.7 | 12 | 20 | 24 | 12 | 18 | 30 | 36 | 18 | - | 35 | 40.5 | 21 | 26 |
|
A類系統──該類系統任何一相導體與地和接地導體接觸時,能在1min內與系統分離 B類系統──該類系統僅包括單相接地故障短時運行的條件,接地故障時間應不超過1h, 但在任何情況下,zui長不超過8h每年接地故障總持續時間不超過125h; C類系統──不屬于A類、B類的系統。 System category A──This category comprises those systems in which any phase conductor that comes in contact with earth or an earth conductor. is disconnected from the system within 1 min. System category B ──This category comprises those system which,under faultconditions,are operated,are operated for ashorttimewith one phase earthed.This period should not exceed 1 h..Fora longer period, not exceeding 8h on any occasion, can be tolerated.The total duration of earth faults in any year should not exceed 125h. /5960111 System categeory C──This category comprises all systems which do not fall into A and B 電纜的型號Type of cable |
型號 Type | 名稱 Designation | 適用范圍 Application | YJV | 銅芯交聯聚乙烯絕緣氯乙烯護套電力電纜 Copper conductor,XLPE insulated and PVC sheathed power cable | 室內、隧道及電纜溝等場所,不能承受機械外力。單芯電纜不允許敷設在磁性管道中。 For laying indoors 、 intunnel or cable trench,unable to bear external mechan-icalforces.Single-core cable in magnetic duct is not permissible | YJLY | 鋁芯交聯聚乙烯絕緣乙烯護套電力電纜 Aluminium conductor, XLPE insulated and PVC sheathed power cable | YJY | 銅芯交聯聚乙烯絕緣氯乙烯護套電力電纜 Copper conductor ,XLPE insulated and PEsheathed power cable | YJLY | 鋁芯交聯聚乙烯絕緣氯乙烯護套電力電纜 Alumimium conductor ,XLPE |
|
產品介紹:高壓交聯電纜產品具有傳輸容量大,工作溫度,不受落差的限制,安裝敷設方便等特點,廣泛應用于工礦企業和城市電網中。高壓交聯電纜主要用于電力、建筑、工礦、冶金、交通等部門的動力、照明輸配電系統,由于聚乙烯是電絕緣性能的塑料,加上經過高分子交聯后成為熱固性材料,因此其電性能好,機械性能和耐熱性好。近二十年來,已成為中國中、高壓電纜的主導品種,產品適用于6——35KV的各個電壓級中它可分為:YJV-交聯聚乙稀絕緣聚氯乙烯護套電力電纜,YJV22-交聯聚乙烯絕緣鋼帶鎧裝高壓電纜,YJLV-交聯聚乙烯絕緣鋁芯鋼帶鎧裝高壓電纜。
執行標準:GB/T12706-2002
使用特性
· 工頻額定電壓U0/U為6kv/10kv~26/35kv。
· 電纜導體的zui高允許工作溫度:90℃。
· 短路時(zui長時間不超過5s)電纜導體的zui高溫度不超過2500C。
· 電纜敷設時環境溫度應不低于00C。
· 電纜彎曲半徑:三芯電纜不小于電纜外徑15倍;單芯電纜不小于電纜外徑20倍。
電纜額定電壓的選擇
· 電纜的額定電壓應適合于電纜系統的運行狀況,用U0/U(Um)kv表示。
U0-電纜設計用的導體對地或金屬屏蔽之間的額定工頻電壓;
U-電纜設計用的導體間的額定工頻電壓;
Um-設備可承受的“zui高系統電壓"的zui大值。
產品參數:
導體標稱截面 | 絕緣 厚度 | 護套 厚度 | 電纜近似外徑 | 電纜近似重量 | 20℃ 導體 | 電纜載流量 | 短路電流 |
直流 電阻 | 在空 氣中 | 直埋土壤中 | 導 體 | 屏蔽層 |
銅帶 | 銅絲 |
mm 2 | mm | mm | mm | kg/km | Ω/km | A | A | KA | KA | KA |
3×25 | 3.4 | 2.4 | 48 | 3190 | 0.727 | 120 | 125 | 3.69 | 2.958 | - |
3×35 | 3.4 | 2.5 | 50 | 3731 | 0.524 | 140 | 155 | 5.15 | 2.958 | - |
3×50 | 3.4 | 2.6 | 53 | 4396 | 0.387 | 165 | 180 | 7.31 | 2.958 | - |
3×70 | 3.4 | 2.7 | 57 | 5198 | 0.268 | 210 | 220 | 10.2 | 2.958 | - |
3×95 | 3.4 | 2.9 | 62 | 6350 | 0.193 | 355 | 265 | 13.8 | 2.958 | - |
3×120 | 3.4 | 3 | 65 | 7257 | 0.153 | 290 | 300 | 17.4 | 2.958 | - |
3×150 | 3.4 | 3.1 | 69 | 8383 | 0.124 | 330 | 340 | 21.7 | 2.958 | - |
3×185 | 3.4 | 3.2 | 72 | 9741 | 0.0991 | 375 | 380 | 26.7 | 2.958 | - |
3×240 | 3.4 | 3.3 | 78 | 11854 | 0.0754 | 435 | 435 | 34.6 | 3.301 | - |
3×300 | 3.4 | 3.4 | 84 | 14861 | 0.0601 | 495 | 485 | 43.1 | 3.301 | - |
|
|
|
|
|
|
|
|
|
|
|